Description
These power distribution and switching devices cater to access control systems and related components. They transform a 115VAC 60Hz input into eight independently managed 12VDC or 24VDC outputs, each safeguarded by fuses. These outputs can be configured to dry contact Form C. Activation of outputs occurs through an open collector sink or a normally open (NO) dry trigger input from various access control equipment such as card readers, keypads, push buttons, or passive infrared sensors (PIRs). These units efficiently deliver power to access control hardware like magnetic locks, electric strikes, and magnetic door holders. They support both fail-safe and fail-secure operational modes. The Fire Alarm Control Panel (FACP) interface facilitates emergency egress and alarm monitoring, and can also initiate other auxiliary devices. Furthermore, the fire alarm disconnect function can be individually set for any or all of the eight outputs.